1. Input signal

Input: 12 way 0~250V Voltage. The input signal is DC OR AC(Frequency 25~75Hz).Or 12 ways 0~200mA Current。Input signal is DC OR AC  (Frequency 25~75Hz).

Signal processing:16-bit A/D Sampling;Sample rate: 3000 Times/S.Output true valid value

Data update period:Settable;range is 67mS~1.7S,default update time is 1.44S;

Overload capacity:1.2 times of measuring ranges can be measured correcty;Over 2 times of measuring ranges can input 1s, but not damaged.

Isolation:Isolated between signal input and output communication ports, isolation voltage is 000V DC. DATA+、DATA-、VCC、GND are output terminals, common grounding with GND,12 ways signal, input common ground terminal is AGND.

2. Communication output

Ports:RS-485,two-wire system, ±15KV ESD protection

Protocol:MOSBUS-RTU、ASCII and so on

Rate:1200、2400、4800、9600、19200 Bps,can be set by software.

Module add:00~FF can be set by software.

3.Measuring accuracy: 0.2 grade;(Input is 50Hz or DC signal)

4.Module power: +8~24V DC

5.Power:Typical power is45 mA.

6.Work conditions:

Work Temp.:-20℃~70℃;

Storage temp.:-40℃~85℃;

Relative humi.:-5%~95% No condensation

7.Installation:

DIN rail mounted, Size:122mm *70mm * 43mm.